Troubleshooting and Fault correction
Instruction handbook b maXX (BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08
71
of 82
10
3rd level
error messages
P0240 to P0244 Error in function module A to E
NOTE!
3rd level errors are only displayed in ProDrive separated by a decimal point from the
corresponding 2nd level error (refer to
ZAbbildung 28– auf Seite 69).
e.g.:
Motor error 102: Group error find notch position (2nd level)
Find notch position error 102.64: Drive moved more than 4 times delta angle.
(3rd level)
Error No. Meaning Reaction Troubleshooting
0 reserved error
1 Module not identified no
reaction
Check if the right module is plugged at the right posi-
tion
2 Identified module is not permitted at this posi-
tion
no
reaction
3 Digital output short-circuited or 24V supply not
connected to the DIO module
no
reaction
Check the cabling of the digital outputs
4 Invalid target parameter value caused by digital
input
no
reaction
Check the parameterization of the input channel
5 Direct PLC-IO access for this module not per-
mitted
no
reaction
Don’t select the module
6 Required module is missing, only for BM4100
active mains rectifier unit
Pulse
stop
Connect the required module for operation with active
mains rectifier - see operation handbook b
maXX
BM4100 active mains rectifier unit
7 Module must not be used for actual active
mains rectifier unit mode or controller mode
no
reaction
8 Reserved no
reaction
9 Too much Analog-IO-Modules connected no
reaction
More than 2 analog modules are not allowed
10 AIO-04: current < 4 mA no
reaction
Current source not connected, disconnection or short-
circuit
11 AIO-04: current > 20 mA no
reaction
Current source impress too much current