Page58
AllCircuits/OutletsPowerFactorThreshold
AllCircuits/OutletsPowerThreshold
O
utlet Circuit Threshold Menu
Device 1, Outlet 1
Efficiency Threshold: 100, Power Threshold: 10
Power/VA Power Factor Threshold....1
Minimum Power Threshold............2
Enter Request :
Unit displays the Outlet Circuit
Threshold Menu with Device Outlet
number and current values.
Select 2), to change the Minimum
Power Threshold level. Enter a value.
Factory Default is (50w).
Minimum power required to generate an SNMP power factor
trap if power factor is below threshold.
Enter threshold value:
This option allows user to set all circuits and outlets to the same Power Factor Threshold levels.
(MMX) refers to the metered-outlet modular- series. Default Value = (0%)
Power/VA ratio threshold as a percent, between 0 and 100, inclusive.
Power factors below this value will generate an SNMP trap, if enabled and
power is
above minimum power threshold. A value of 0 disables threshold.
Value will be applied to all circuits and outlets (MMX units).
Enter threshold value:
This option allows user to set all circuits and outlets to the same Power Threshold levels. (MMX) refers
to the metered-outlet modular series. Default Value = (50w)
Minimum power required to generate an SNMP power factor
trap if power factor is below threshold.
Value will be applied to all circuits and outlets (MMX units).
Enter threshold value:
Setting all Power/VA Efficiency Thresholds to 80%
Power Factor Threshold Menu
Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level
Sel M/P Identifier Cks #Outs
1 2/1 MMP-27 6 24
2 All
Circuits/Outlets - Power Factor Threshold
3 All Circuits/Outlets - Power Threshold
Enter Request :
The unit responds with
message stating the
Thresholds were set to
the new value and
displays the Menu.