F20: Jog Frequency
Range: 0 - 400 Hz (Default: 10.00Hz)
Description: This parameter sets the frequency for Jog operation. It cannot be set above
F21 (Max. frequency). Jog operation overrides all other applications except
Dwell operation. Therefore, if Jog frequency command is entered in the
middle of Multi-step, Up-Down or 3-wire operation, operation is executed
at Jog frequency.
Set the desired jog frequency in F20.
Select a terminal from P1 - P8 to use for this setting.
If P5 is set for Jog operation, set I21 to 4 (Jog).
Jog frequency can be set within the range of F21 (Max. frequency) and
F22 (Start frequency).
See I21 (Multi-function input terminal P5 define, page 114)
F21: Maximum Frequency
Range: 40 - 400 Hz (Default: 60.00Hz)
Description: This parameter sets the highest frequency the drive can output. It is
frequency reference for Accel/Decel (See H70, page 101).
CAUTION: Any frequency cannot be set above F21 (Max. frequency)
except F22 (Base frequency).
If H40 (page 95) is set to 3 (sensorless vector), Max. frequency is settable
up to 300Hz.
71
6 - Parameter Descriptions
P4-CM
ON
Time
Time
FX-CM
ON
Time
RX-CM
ON
Time
Output Frequency
ON
5Hz
5Hz
Jog Frequency