F22: Base Frequency
Range: 30 - 400 Hz (Default: 60.00Hz)
Description: The drive outputs its rated voltage to the motor at this frequency (see motor
nameplate).
F23: Start Frequency
Range: 0 - 10Hz (Default: 0.50 Hz)
Description: The drive starts to output its voltage at this frequency. If a frequency is set
lower than this, 0.00 Hz is automatically set. For example, if F23 is set to
5Hz, the drive starts running when the reference frequency is 5Hz.
F24: Frequency High/Low Limit Select
Range: 0 - 1 (Default: 0)
Description: This parameter activates the high and low frequency (see F25 & F26).
72
6 - Parameter Descriptions
Consult with the motor manufacturer before exceeding the
base speed of the motor. Verify that the driven equipment
can operate at the maximum speed set.
CAUTION
Output Voltage
Rate Voltage
Output Frequency
Start
Frequency
Base
Frequency
Maximum
Frequency