F25: Frequency High Limit
Range: 0 - 400 Hz (Default:60.00)
Description: This parameter sets the high limit frequency. It cannot be set above F21
(Max. Frequency). It is only displayed when F24 (Frequency high/low limit
select) is set to 1. This setting is also valid when frequency setting is done
via keypad. When frequency setting is done via Analog input (voltage or
current input), the drive operates within the range of high and low limit
frequency as shown below.
Set F24 to 1.
Active run frequency can be set within the range of F25 and F26.
F26: Frequency Low Limit
Range: 0.1 - 400 Hz (Default: 0.50Hz)
Description: This parameter sets the low frequency (see parameter F25 for more
information).
73
6 - Parameter Descriptions
Freq.
V1(Voltage input)
Max freq.
0 20mA
10V
I (Current input)
High limit
freq.
Low limit
freq.
When freq. limit is not
selected