H22 [Speed Search selection] selects the speed search function - set to 1.
•
H23: Limits current during Speed search. Set as the percent of H33.
•
H24 & H25: Speed search is activated via PI control. Adjust P gain and I
gain corresponding to the load characteristics. Set this value considering
the load inertia set in H37.
•
I54 & I55: Signal that is active via multi-function output terminal (MO)
and multi-function relay output (3AC).
Related Functions:
H20 [PowerON Start]
H21 [Restart after Fault Reset]
H26 - H27 [Auto Restart]
H30 - H37 [Motor Parameters]
89
6 - Parameter Descriptions
Input Power
Time
Motor Speed
Time
Output Frequency
Output Voltage
Time
Time
Input Power loss