Operation mode standard, parameter
Operation mode
440 = 1
This operation mode can be used, for example, for pressure or volumetric flow con-
trol with linear operation behavior.
The minimum value monitoring prevents an acceleration of the drive if the actual
value is missing.
If the actual value is missing (< 0.5%) the output frequency is guided to the Mini-
mum frequency
418. This is done using the set Deceleration (clockwise) 421.
If the actual value is available again, the controller continues operation automatically.
Technology
Controller
Act. Percentage
Source 478
Ref. Percentage
Channel
Ref. Percentage
Source 476
Minimum value
> 0.50%
P.478
0.50%
<
Amplification 444
P
Derivative Time 618
I
Integral Time 445
+
+
-
Max. P-Component
Difference
1
0
Limitation
Max.
I-Component
Fixed
Frequency