EasyManuals Logo

BONFIGLIOLI ACTIVE Cube ACU 201-01 User Manual

BONFIGLIOLI ACTIVE Cube ACU 201-01
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
4.8 ACU 401 (5.5 to 15.0 kW, 400 V)
Type
ACU 401
-19
-21
-22
-23
-25
Construction Size
3
4
Output, motor side
Recommended motor shaft power
P
kW
5.5
7.5
9.2
11.0
15.0
Output current
I
A
14.0
18.0
22.0
3)
25.0
32.0
Long-term overload current (60 s)
I
A
21.0
26.3
30.3
37.5
44.5
Short-time overload current (1 s)
I
A
28.0
33.0
33.0
50.0
64.0
Output voltage
U
V
Maximum input voltage, three-phase
Protection
-
-
Short circuit / earth fault proof
Rotary field frequency
f
Hz
0 ... 1000, depending on switching frequency
Switching frequency
f
kHz
2, 4, 8, 12, 16
Output, brake resistor
Min. brake resistance
R
Ω
48
48
48
32
32
Recommended brake resistor
(U
dBC
= 770 V)
R Ω 80 58 48 48 32
Input, mains side
Mains current
2)
3ph/PE
I
A
14.2
15.8
1)
20.0
1)
26.0
28.2
1)
Mains voltage
U
V
320 ... 528
Mains frequency
f
Hz
45 ... 66
Fuses
I
A
16 25 35
UL type 600 VAC RK5
I
A
20
30
40
Mechanics
Dimensions
HxWxD
mm
250 x 100 x 200
250 x 125 x 200
Weight (approx.)
m
kg
3.0
3.7
Degree of protection
-
-
IP20 (EN60529)
Terminals
A
mm
2
0.2 ... 6
0.2 ... 16
Form of assembly
-
-
vertical
Ambient conditions
Energy dissipation
(2 kHz switching frequency)
P W 145 200 225 240 310
Coolant temperature
T
n
°C
0 ... 40 (3K3 DIN IEC 721-3-3)
Storage temperature
T
L
°C
-25 ... 55
Transport temperature
T
T
°C
-25 ... 70
Rel. air humidity
-
%
15 ... 85, not condensing
If required by the customer, the switching frequency may be increased if the output current is reduced at the
same time. Comply with the applicable standards and regulations for this operating point.
Output current
4)
Frequency inverter nominal power
Switching frequency
2 kHz
4 kHz
8 kHz
12 kHz
16 kHz
5.5 kW
14.0 A
14.0 A
14.0 A
11.8 A
9.5 A
7.5 kW
18.0 A
1)
18.0 A
1)
18.0 A
1)
15.1 A
1)
12.2 A
9.2 kW
1)
23.0 A
22.7 A
3)
22.0 A
3)
18.5 A
3)
15.0 A
3)
11 kW
25.0 A
25.0 A
25.0 A
21.0 A
17.0 A
15 kW
32.0 A
1)
32.0 A
1)
32.0 A
1)
26.9 A
1)
21.8 A
1)
Three-phased connection demands mains commutating choke
2)
Mains current with relative mains impedance ≥ 1% (see chapter „Electrical installation“)
3)
Reduction of switching frequency in thermal limit range
4)
Maximum current in continuous operation
06/13 Operating Instructions ACU 37

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI ACTIVE Cube ACU 201-01 and is the answer not in the manual?

BONFIGLIOLI ACTIVE Cube ACU 201-01 Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelACTIVE Cube ACU 201-01
CategoryInverter
LanguageEnglish

Related product manuals