86 en | Installing Access Modular Controller 2
2020-01 | V02 | Installation manual Bosch Access Systems V.B.
R
P
1k 1k2 1k5 1k8 2k2 2k7 3k3 3k9 4k7 5k6 6k8 8k2
R
S
8k2 1500 1650 1700 1800 1900
Table4.12: Maximum values of cable resistance per used resistor combination in Ohm
Notice!
For UL Access controls installations, only the R
S
= 2k2 and R
P
= 2k2 End-of-Line resistors may
be used.
Notice!
We recommend using serial resistors (R
S
) no higher than 5K6 in order to obtain clear
measurements.