9 Fire alarm
Notice!
Detailed information about types of alarms, alarm delays and the panel controller display can
be found in
Alarm, page 35
.
This chapter contains information about the following points:
–
Optical and acoustic signals, page 42
–
Acknowledging a message, page 42
–
Silence internal buzzer, page 42
–
Activate and silence signaling devices, page 42
–
Resetting signaling devices and transmission devices, page 42
–
Triggering fire verification, page 43
–
Resetting alarm message, page 44
–
Bypassing detectors, page 45
Signaling fire alarms
A fire alarm is signaled optically and acoustically on the panel through:
– Displaying the logical zones on the display
– Lighting up the "Alarm" LED icon
– An internal buzzer sounds on the system.
Notice!
Alarm messages have the highest priority compared with all other message types. If a fire
alarm is reported, the system switches automatically to alarm indication.
9.1 Evacuation
You can manually control all available evacuation zones.
Press the evacuation button to open the list with all available evacuation zones. To
search for a specific zone, enter the number of a group of notification appliances and press
.
Notice!
The individual control of each group is only possible for panel controllers with a premium
license.
Select the required group to start or stop the evacuation of this zone immediately. Use
and to scroll through the list. The group entries change their background color
according to their current state.
Select All On to control all evacuation groups or All Off to stop the activation of all groups at a
time.
The background colors of the groups have the following meaning:
– Red: Groups which are actively being controlled in case of an alarm