11 Bypass
This chapter contains information about the following points:
Bypassing and un-bypassing elements, page 51
Displaying and un-bypassing bypassed element groups, page 51
Displaying list of all bypassed elements, page 52
Bypassing/Un-bypassing buzzer, page 52
Bypassing/Un-bypassing the output to fault warning routing equipment, page 53
!
Warning!
All alarm and fault messages from bypassed detectors are no longer displayed.
11.1 Menu overview
Bypass
Block
-> Bypass -> Show bypassed
devices
Select by
number
Bypass buzzer Printer
Block NAC Transmission
device
HVAC Doorholder
Detector Logical zone Extinguishing
system
Annunciator
Bypass group More... -> Control
element
Interface
module
11.2 Bypassing and un-bypassing elements
Select the element you require in the submenu.
i
Notice!
Partly bypassed elements, such as loops or bypass groups, can be displayed and completely
bypassed; see
Displaying and un-bypassing bypassed element groups, page 51
.
i
Notice!
The menu structure may be different depending on the configuration in FSP-5000-RPS.
i
Notice!
Depending on the configuration and the structure of the panel, it is possible that signaling
devices cannot be bypassed individually but only all at once. In this case, the NACAll list field
is offered instead of a selection list.
11.3 Displaying and un-bypassing bypassed element groups
1. There are two ways to display all partly or completely bypassed loops, logical zones etc.:
Select Bypass on the status bar
A list of various states is displayed. Or
Select Bypass Block in the start menu.
2. Select either Bypassed or Bypass and then Show bypassed devices.