EasyManuals Logo

Bosch AVENAR 8000 User Manual

Bosch AVENAR 8000
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Diagnostics | en 59
Bosch Sicherheitssysteme GmbH User Guide 2020-07 | 3.0 | F.01U.378.877
3. Routing table
A table with routing information is displayed.
All networked nodes that can be reached via the node currently being operated and that are
recognized within the system network are displayed under Node.
CAN1 to USB1 designate the interfaces on the currently operated panel node. In this example,
it is the node 1 interfaces.
The type of interface on the panel node currently being operated is listed under interface.
The following interfaces can be designated:
CAN 1 interface
CAN 2 interface
Ethernet 1 (IP multicast or UDP tunnel)
Ethernet 2 (IP multicast or UDP tunnel)
Ethernet 3 (IP multicast or UDP tunnel)
Ethernet 4 (IP multicast or UDP tunnel)
USB 1 interface
The number of nodes that need to be passed in order to reach the listed node is entered
under distance. For nodes that are directly reachable via IP multicast, the value is 1; for nodes
that are connected via other interfaces (e.g. CAN) to nodes reachable via IP multicast, the
value is increased in increments accordingly (e.g. connected via IP multicast + CAN1/CAN2,
value = 2).
A physical node number from 1 to 64 can be assigned to panels.
13.7.2 Consistency check
Inconsistencies between the network settings configured in FSP-5000-RPS and those set in
the panel controller are displayed under Diagnostics - Network services -
Consistency check.
1. In the start menu, select Diagnostics
2. Network services
3. Consistency check
Where inconsistencies are identifiable between the network settings saved in the panel
controller and those configured in FSP-5000-RPS, these are indicated. You can use the
arrow key on the display to alternate between displaying Problems of active
configuration: and Problems expected after restart:.
Problems of active configuration:
The table indicates inconsistencies between the network settings of the panel controller's
active configuration ("active") and the settings configured in RPS ("configured").
Problems expected after restart:
The table indicates inconsistencies between the network settings that have already been
configured on the panel but which do not take effect until restart ("saved") and the settings
configured in RPS ("configured").
13.7.3 Ethernet ports
To display a table listing the various parameters and the status of the two Ethernet ports:
1. In the start menu, select Diagnostics
2. Network services
3. Ethernet ports
Information on Ethernet port 1 is displayed.
You can use the arrow key on the display to switch to details of Ethernet port 2, port 3
and port 4.
To update the information displayed, select Refresh.

Table of Contents

Other manuals for Bosch AVENAR 8000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch AVENAR 8000 and is the answer not in the manual?

Bosch AVENAR 8000 Specifications

General IconGeneral
Number of Detectors per Loop254
Number of Control Panel per Network32
IP CommunicationYes
Resolution800 x 480 pixels
TouchscreenYes
Operating SystemLinux-based
Memory512 MB RAM, 4 GB Flash
Power Supply24 V DC
Protection ClassIP30
Loop Capacity4 loops
ConnectivityEthernet, USB, RS485
Panel TypeModular fire alarm panel