14 Maintenance
This chapter contains information about the following points:
Walktest: see
Maintenance – walktest, page 67
Change language, page 65
Activate Outputs, page 65
Activate Transmission Device, page 66
Detector removal
History Log: see
Maintenance – history log, page 71
Bypassing/Un-bypassing buzzer, page 66
14.1 Menu overview
Maintenance -> Walktest Change language
Activate outputs Activate transmission device
History log Bypass buzzer
14.2 Change language
i
Notice!
The fastest way to change the language display is via a shortcut; see also
Changing language
display, page 29
.
There are two ways of selecting a different language display:
Using the menu
Entering a shortcut; see
Changing language display, page 29
.
i
Notice!
After the system starts up following a power cut or battery failure, the default language
defined in the FSP-5000-RPS programming software is set again.
Making a selection via the menu
1. In the start menu, select Maintenance
2. Change language
A list of the languages which can be selected is displayed.
3. Select the language you require.
The displays are displayed in the selected language.
14.3 Activate Outputs
1. In the start menu, select Maintenance
2. Activate outputs
Various element categories are displayed.
3. Select a category or Select by number and enter the number of the element into the
search screen; see also
Search Function/Element, page 27
4. Select the required list fields. The list fields are marked.
5. Select On to activate the selected notification appliances.
The selected signaling devices are activated.
6. Select All to activate all notification appliances.
7. To end activation of the selected elements, repeat the same steps but select Off in step