48 en | Fault message
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877 User Guide Bosch Sicherheitssysteme GmbH
– Date and time of the message
– Physical and logical addressing of the element
– Only for LSN detectors: specification of the detector type
– Action text (depending on the configuration)
Select OK to return to the list of all fault messages. Reset, see
Resetting fault message, page
48
.
Block, see
Blocking an element, page 49
. Select Details (if available) to go directly to the
respective Diagnostics window for troubleshooting, see
Diagnostics, page 56
.
10.2.8 Signals
Optical signals
The "fault" icon lights up yellow.
Depending on the type of fault, an additional yellow signal light lights up (see also
Status
LEDs, page 14
):
– Fault system (LED steady)
– Fault power (LED steady)
– Fault detector (LED blinking)
– Fault transmission device (LED blinking)
– Fault signals (LED blinking)
– Output to fire protection equipment fault (LED blinking)
Acoustic signal
An internal signal tone sounds on the system.
To temporarily silence the internal buzzer:
Press .
10.3 Resetting fault message
Caution!
If a message does not have to be reset, it is removed from the display as soon as the fault has
been rectified.
Depending on the configuration, three different variants are offered for resetting; see
Resetting alarm message, page 43
.
There are two ways to reset a fault message:
– Select Reset in the message display or
– Select the fault message and then press Reset in the detailed view
The selected element/element group is reset.
If a list field is marked with an "R", the process of resetting is not yet complete for this
element.
TEXT R
If an element cannot be reset, it will continue to be displayed in the list.
After the successful resetting of all elements, the standby display is displayed.