The diagnostic information displayed depends on the voice alarm system configured for the
AVENAR panel 8000/2000.
1. In the start menu, select Diagnostics.
2. Select VAS.
One of the following VAS will be displayed:
13.8.1 Plena
The following information is displayed:
– Trouble (yes/no)
– Emergency (yes/no)
– Failure (yes/no)
– Internal monitoring (yes/no)
– Supervision time (sec).
– Boot-up phase is finished (yes/no)
– Failure at controller (yes/no)
– Failure at router (yes/no)
13.8.2 PAVIRO / Praesideo
OIP service: Shows if the panel has access to the OIP service.
– OK: OIP service is running on the fire panel.
– Disconnected: OIP service is not running. Reset the fire panel through the user interface.
Connection status: Shows if the panel has established a connection to the VAS.
– Connected: Connection is established.
– Disconnected: Connection is not established.
Status of VAS over IP: Shows if the connected VAS has reported a fault condition.
– n/a: Not possible to execute the check, for instance due to interrupted connection
– OK: No fault condition is reported by the VAS.
– Fault: The connected VAS reports a fault condition. Check the VAS. Reset the fault on the
VAS.
License: Software check if the fire panel contains a premium license.
– OK: Premium license is available.
– Missing: Premium license is not available. Exchange standard license by premium license.
– Disconnection in x hours: In case the premium license is missing, the system will
automatically interrupt the connection to the VAS after 72 hours. The counter shows the
remaining time.
Trigger configuration: Software check if the configured virtual VAS triggers are available as
virtual inputs in the VAS configuration.
– n/a: Not possible to execute the check, for instance due to interrupted connection
– OK: All virtual VAS triggers are available as virtual inputs in the VAS.
– Mismatch: Virtual VAS triggers are not corresponding to the virtual inputs available in the
VAS. Verify the configuration.
Compatibility: Shows if the firmware version of the connected VAS is released for the
connection to a fire panel.
– n/a: Not possible to execute the check, for instance due to interrupted connection
– OK: VAS is suitable.
– Warning: Check the firmware version of the VAS.
Connection fault counter: Shows the number of connection faults of the interface since the
last reboot of the panel.
Address of VAS over IP: Configured IP address of the VAS.