Easy Series (ICP-EZM2) | Installer Guide | 2.0 Installation
.
Bosch Security Systems, Inc. | 5/07 | F01U025147-01 15
2.6.2 Intrusion Point Wiring
Refer to the figures below to wire Supervised Points 1 to 32 as wired or wireless intrusion points.
To program Supervised Points 1 to 32 as intrusion points, refer to Section 4.2.1 Points on page 31.
For fire point configuration, refer to Section 2.6.1 Fire Point Wiring on page 14.
3
1
2
4
2 3
1
45
2 3
1
4
5
6
Single 2.2 k
Ω
EOL resistor
1 - Supervised point
(on-board, DX2010, or
wireless input)
2 - 2.2 k
Ω
EOL resistor
3 - Alarm terminals
(Normally Open)
4 - Alarm terminals
(Normally Closed)
Dual 2.2 k
Ω
Resistors
(Point Tamper*)
1 - Supervised point
(on-board, DX2010, or
wireless input)
2 - Alarm terminals
(Normally Closed)
3 - Tamper terminals
(Normally Closed)
4 - 2.2 k
Ω
EOL resistor
5 - 2.2 k
Ω
alarm resistor
* This option is not allowed by UL.
Dual 2.2 k
Ω
Resistors
(Point Tamper*)
1 - Supervised point (on-board,
DX2010, or wireless input)
2 - Alarm terminals
(Normally Closed)
3 - Tamper terminals
(Normally Closed)
4 - 2.2 k
Ω
end-of-line resistor
5 - 2.2 k
Ω
alarm resistor
6 - Additional devices
(up to 4 maximum)
* This option is not allowed by UL.
2.6.3 Keyswitch Wiring
Refer to the figure below to wire Supervised Points 1 to 32 as keyswitch points (Point 2 shown in figures).
To program Supervised Points 1 to 32 as keyswitch points, refer to Section 4.2.1 Points on page 31.
3
1
2
3
1
2
Single 2.2 k
Ω
end-of-line resistor option
1 - Supervised point
(on-board, DX2010, or wireless device)
2 - 2.2 k
Ω
resistor
3 - Normally-open momentary or maintained
keyswitch
Dual 2.2 k
Ω
resistors (point tamper option
)
1 - Supervised point
(on-board, DX2010, or wireless device)
2 - 2.2 k
Ω
resistor
3 - Normally-closed momentary or
maintained keyswitch