Easy Series (ICP-EZM2) | Installer Guide | 4.0 Programming
32 Bosch Security Systems, Inc. | 5/07 | F01U025147-01
4.2.2 Report Configuration
Report
Configuration
[1]
Account Number
[2]
Report Destination
[1]
Route 1 Primary
[2]
Route 1 Backup
[3]
Route 2 Primary
[4]
Route 2 Backup
Format
Format
Format
Format
Phone Number
Phone Number
Phone Number
Phone Number
[#] Exit
[#] Exit
[#] Exit
[#] Exit
Route 1
Route 2
[#] Exit
To configure reports:
1. Enter a four- or six-digit account number.
The account number applies to all report
destinations.
2. Select a report destination.
[1] = Route 1 Primary
[2] = Route 1 Backup
[3] = Route 2 Primary
[4] = Route 2 Backup
3. Select a format option for the report
destination.
[1] = Select first option.
[2] = Hear next option.
4. Enter a phone number for the report
destination.
5. Repeat Steps 2 to 4 for additional report
destinations.
6. Refer to Section 4.3.4 Report Routing
Programming Items on page 43 to enable
or disable reports.
Account Number Entries:
Entry Key Press
0 to 9 [0] to [9]
B [*][1]
C [*][2]
D [*][3]
E [*][4]
F [*][5]
Phone Number Entries:
Entry Key Press
0 to 9 [0] to [9]
* [*][*]
# [*][#]
Pause [*][1]
Exit with Save [#]
Exit without Save [#][#]
1
Disable phone number [0][#]
1
Press [#] twice within two
seconds to exit without saving your
entry.
Format Options:
• Disabled (default)
• Contact ID
• SIA
• Voice
• SMS Text (TAP)*
• Fast Format
* SMS Text Messages:
• Intrusion Alarm
• Fire Alarm
• System On
• System Off
• Point Trouble
• System Trouble
• Test Report
• Restoral
• Keypad
SMS providers do not
guarantee delivery of SMS
text messages.
Record report configuration programming entries in Section 4.3.3 Communicator Programming