4.3.1 ROM Firmware Version Items
Programming Item Item Number Description
Control Panel Firmware Version 090
System announces the installed firmware version.
This item is read-only.
Control Center 1 Firmware Version 091
Control Center 2 Firmware Version 092
Control Center 3 Firmware Version 093
Control Center 4 Firmware Version 094
System announces the installed firmware version for the selected
control center. These items are read-only.
4.3.2 System Programming Items
Programming Item
Item
Number
Description (Range) Entry
Country Code 102
Select the appropriate code for country-specific operation and
programming defaults (00 to 65).
58
Enclosure Tamper
Enabled
103 0 = Enclosure tamper input disabled
1 = Enclosure tamper input enabled
1
Fire Bell Cut-Off Time 107
Enter how long the fire alarm sounds at bell outputs and at the control
center (0 to 90 min).
5
Intrusion Bell-Cut off
Time
108
Enter how long the intrusion alarm sounds at bell outputs and at the
control center (0 to 90 min).
5
Intrusion Abort
Window
110
Enter how long the control panel waits to send an alarm report after
an alarm occurs (15 to 45 sec).
30
Intrusion Cancel
Window
112 Enter how long a user has to cancel an intrusion alarm report after the
system sends the report to the central station (5 to 10 min).
5
Chime Tone Select 114 Select a Chime tone:
1 = Chime door bell
2 = Single chime
3 = Standard door bell
1
Chime Mode
Operation After
System Off
115 Determines Chime Mode operation after the system is turned off.
0 = Off
1 = On
2 = Follows previous setting (either on or off)
0
Automatic Test Report
Frequency
116
Determines how often the control panel sends the automatic test
report.
0 = No automatic test report
1 = Daily (refer to Programming Items 143 and 144 on page 40)
2 = Weekly (refer to Programming Item 145 on page 40)
3 = Monthly (refer to Programming Item 146 on page 40)
0
123456
RPS Passcode 118
Enter the 6-digit passcode that allows access to the control panel
from RPS. Use digits 0 to 9 and A to F.
Daylight Saving Time
Operation
121
0 = No time adjustment
1 = North America
(prior to 2007)
2 = Europe and Asia
3 = Tasmania, Australia
4 = Rest of Australia
5 = New Zealand
6 = Cuba
7 = South America and
Antarctica
8 = Namibia, Africa
9 = USA after 2006
1
Default
= Country-specific default. Select this programming item to hear the updated default value.