Easy Series (ICP-EZM2) | Installer Guide | 7.0 Reference Materials
70 Bosch Security Systems, Inc. | 5/07 | F01U025147-01
Quick Reference
Refer to the following table for programmable features, shipping defaults, and recommended programming
that comply with the ANSI/SIA CP-01 False Alarm Reduction standard.
The system test button tests all points, all outputs, the control panel, and the communicator. Refer to Section 5.0
System Test on page 56 for more information.
Paragraph
Number in
ANSI/SIA CP-01 Feature Requirement Range
Shipping
Default
Recommended
Programming
1
4.2.2.1 Exit Time
Required
(programmable)
For full or auto arming: 45 sec to
2 min (255 sec max)
60 sec 60 sec
4.2.2.2
Progress
Annunciation/
Disable for Silent Exit
Allowed
Individual control centers can be
disabled.
All control
centers
enabled.
All control
centers enabled.
4.2.2.3 Exit Time Restart Required option For re-entry during Exit Time Enabled Enabled
4.2.2.5
Auto Stay Arm on
Unvacated Premises
Required option
(except for
remote arm)
If no exit after full arm Enabled Enabled
4.2.4.4
Exit Time and
Progress
Annunciation/
Disable for Remote
Arm
Allowed option
(for remote arm)
Can be disabled for remote arm Enabled Enabled
4.2.3.1 Entry Delay(s)
Required
(programmable)
30 sec to 4 min
2
30 sec At least 30 sec
2
4.2.5.1
Abort Window for
Non-fire Zones
Required option
Can be disabled by zone or zone
type
Enabled
Enabled
(all zones)
4.2.5.1
Abort Window Time
for Non-fire Zones
Required
(programmable)
15 sec to 45 sec
2
30 sec At least 15 sec
2
4.2.5.1.2 Abort Annunciation Required option
Annunciate that no alarm was
transmitted
Enabled Enabled
4.2.5.4.1 Cancel Annunciation Required option
Annunciate that a Cancel was
transmitted
Enabled Enabled
4.2.6.1 and
4.2.6.2
Duress Feature Allowed option
No 1+ derivative of another user
code; no duplicates of other user
codes
Disabled Disabled
4.3.1 Cross Zoning Required option Programming needed Disabled
Enabled and two
or more zones
programmed
4.3.1
Programmable Cross
Zoning Time
Allowed Can program
Per
manufacturer
Per walk path in
protected
premises
4.3.2 Swinger Shutdown
Required
(programmable)
For all non-fire zones, shut down at
one or two faults
One fault One fault
4.3.2
Swinger Shutdown
Disable
Allowed For non-police response zones Enabled
Enabled
(all zones)
4.3.3
Fire Alarm
Verification
Required option
Depends on control panel and
sensors
Disabled
Enabled unless
sensors can self-
verify
4.5 Call Waiting Cancel Required option Depends on user phone line Disabled
Enabled if user
has call waiting
1
Programming at installation site might be subordinate to other UL requirements for the intended application.
2
Combined Entry Delay and Abort Window should not exceed 1 minute.
3
If the cross zone timer ends and a second cross zone point is not faulted, the system sends an intrusion alarm unverified report.