NurseCall Main Unit | en 55
Bosch Security Systems User Manual F.01U.252.699 | V1.1 | 2012.01
Change day / night
If the change day / night is activated, the NurseCall system transfers all alarms during night to
the group 24. During the day, all groups 00 - 24 can be used. When switching from day to
night or vice versa, the message "Day-Night" is sent to the activated pagers.
Priority alarms
The assistance and fire alarms are priority calls sent to all activated pagers.
Call repetition
If alarms or messages are not acknowledged after approximately 7 minutes, call repetitions
are also sent to the group 23.
A.5.2 POCSAG protocol
Characteristics
Data rate: 9600 Bauds
Transmission: asynchronous
10 bit-structure (1 start bit, 7 data bits, no parity, 1 stop bit)
–Simplex mode
Only alarms arriving to the alarm buffer are transmitted, except "Relay Off". Acknowledgement
messages are also transmitted. The transmission is only numeric. Alarms are repeated every 1
or 3 minutes until acknowledgement.
Alarms are sent to the POCSAG user number attributed to the transmitter.
The default group is 00.
NOTICE!
In "floor/room/bed" display mode, use only alpha-numeric pagers which display at least 16
characters.
Group User number
00 001x000
01 001x008
02 001x016
03 001x024
04 001x032
05 001x040
06 001x048
07 001x056
08 001x064
09 001x072
10 001x080
11 001x088
12 001x096
13 001x104
14 001x112
15 001x120