Indicator Description Recommended action Additional information
Message A message fault is
detected.
Switch the voice alarm
controller off and on
again.
See section Message
supervision, page 80.
EMG mic An emergency
microphone fault is
detected.
Check the emergency
microphone. If
necessary, replace it.
See section Emergency
microphone, page 49 and
section Emergency
microphone, page 80.
RCP A remote control panel
fault is detected.
Contact your dealer. This fault should not
occur, since this type of
supervision is disabled.
Router A router fault is
detected.
The indicated fault was
not detected in the voice
alarm controller, but in a
voice alarm router.
Check the voice alarm
routers.
Table 7.2: System fault indicators
100 en | Operation Plena