Bosch Plena - Power Connections: Mains and Back-up

Bosch Plena
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Power
Introduction
The voice alarm controller has the following power connections:
Mains power connection.
Back-up power connection.
Mains power
Proceed as follows to connect the voice alarm controller to the mains power:
4 Select the local mains voltage using the voltage selector on the rear of the voice alarm
controller.
115V~
230V~
Apparatus delivered
Connected for 230V~
Power
Figure 5.16: Voltage selector
Selector
Mains voltage V(AC) Fuse
115 100 - 120 115 V - 10 AT
230 220 - 240 230 V - 6,3 AT
Table 5.3: Voltage selector
Notice!
The Voice Alarm Controller is delivered with the voltage selector in the 230 V position.
1. Put the correct type of fuse in the voice alarm controller.
Notice!
The Voice Alarm Controller is delivered with a T6.3L 250 V fuse for a mains voltage of
220 to 240 V(AC).
2. Connect a locally approved mains cord to the voice alarm controller.
3. Connect the mains cord to a locally approved mains outlet.
5.1.12
62 en | Connection Plena
2013.07 | V2.0 | Installation and Operation manual Bosch Security Systems B.V.