Configuration
A number of functions of the Plena Voice Alarm System is hardware configured using, for
example, DIP switches and volume controls. Other parts of the system must be software
configured using the Plena Voice Alarm System configuration software. A description of this
software is beyond the scope of this manual. This manual only describe the hardware
configuration of a Plena Voice Alarm System.
Notice!
See the Configuration Software Manual for more information about the configuration
software.
It is recommended to do the hardware configuration of the system before the software
configuration.
System settings
The system settings are configured using DIP switches on the rear of the voice alarm
controller. By default, all switches are in the OFF position.
1
2
3
4
5
Off
On
Figure 6.1: System settings DIP switches
No
DIP switch Description
1 Monitor Switches the monitoring loudspeaker on (ON) and off (OFF). See
section Monitor, page 76.
2 APR mode Switches the Asian Pacific Region mode on (ON) and off (OFF). See
section APR mode, page 76.
3 Supervision Switches supervision on (ON) and off (OFF). See section Supervision,
page 76.
4 2ch operation Switches2-channel operation on (ON) and off (OFF). See section 1-
Channel mode operation, page 77 and section 2-Channel mode
operation, page 78.
5 Reserved Reserved. This DIP switch must always be in the OFF position.
Table 6.1: System settings DIP switches
6
6.1
Plena Configuration | en 75
Bosch Security Systems B.V. Installation and Operation manual 2013.07 | V2.0 |