Voice alarm routers
The voice alarm controller has 1 socket for Voice Alarm Routers. Use shielded CAT‑5 Ethernet
cables with RJ45 plugs to connect a voice alarm router to the voice alarm controller. When the
system requires more than 1 voice alarm router, use the system sockets on the voice alarm
router to make loop-throughs. See the connection details below.
The router come with CAN bus termination installed. This is an RJ45 connector with built‑in
termination. Make sure that it is installed in the unused connector. On the routers and call
station the termination switch setting must be in the "ON" position on the last device.
Monitoring
Speaker
ontrol Panel
Router
Warning
T
his apparatus must be earthed
1
2
Firmware upgrade
Design & Quality
The Netherlands
N6
63
Termination
1
...9
ID
Router
Rated input power
Line fuse
Booster 2
In
Out
Made
in China
On
Off
Firmware upgrade
Design & Quality
The Netherlands
N6
63
Termination
1
...9
ID
Router
Rated input power
Line fuse
Booster 2
In
Out
Made
in China
On
Off
Figure 5.3: Connecting routers
Notice!
Each connected voice alarm router must have a unique ID (see section Voice alarm router,
page 82).
Notice!
The voice alarm controller comes delivered with termination plugs (connectors) fitted in some
RJ45 sockets. When connecting routers and RCP panels, the connected device must have
their termination set to on, and the termination plug has to plugged in the unused socket.
5.1.3
Plena Connection | en 51
Bosch Security Systems B.V. Installation and Operation manual 2013.07 | V2.0 |