EasyManua.ls Logo

Bosch Plena - Electrical Specifications: Voice Alarm Controller

Bosch Plena
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Electrical
Voice Alarm Controller
Electrical
Mains voltage: 230/115 V(AC), ± 10%, 50/60 Hz
Mains current: 0.3 A (system idle)
4.0 A (maximum load)
Max. mains inrush current: 6.3 A (for mains voltage of 220 - 240 V)
10 A (for mains voltage of 100 - 120 V)
Battery voltage: 20.0 to 26.5 V(DC)
Battery current: 0.9 A (system idle)
14 A (maximum load)
Notice!
Maximum load means maximum power out, maximum load 24 V(DC) out and maximum
number of call stations.
Message manager
Data format: WAV-file, 16-bit PCM, mono
Supported sample rates (fs): 24 kHz, 22.05 kHz, 16 kHz, 12 kHz, 11.025
kHz
Frequency response:
@ fs = 24 kHz, 100 Hz - 11 kHz (+1/-3 dB)
@ fs = 22.05 kHz, 100 Hz - 10 kHz (+1/-3 dB)
@ fs = 16 kHz, 100 Hz - 7.3 kHz (+1/- 3 dB)
@ fs = 12 kHz, 100 Hz - 5.5 kHz (+1/-3 dB)
@ fs = 11.025 kHz, 100 Hz - 5 kHz (+1/-3 dB)
Distortion: < 0.1% @ 1 kHz
Signal-to-noise ratio (flat at max. volume): > 80 dB
Memory capacity: 64 Mbit Flash
Recording/playback time: 333 s @ fs = 24 kHz
Number of messages: max. 254 wave files
Supervision EEPROM: Continuous checksum control
Supervision DAC: 1 Hz pilot tone
Data retention time: > 10 years
10
10.1
10.1.1
106 en | Technical data Plena
2013.07 | V2.0 | Installation and Operation manual Bosch Security Systems B.V.