Clause / Requirement Compliance Signature
a Evacuate - potentially life-threatening
situation needing immediate
evacuation.
Compliant, if properly installed.
Responsibility of the installer.
b Alert - dangerous situation nearby
requiring warning of pending
evacuation.
Compliant, if properly installed.
Responsibility of the installer.
c Non-emergency - operational
messages, e.g. system test, etc.
Compliant, if properly installed.
Responsibility of the installer.
The use of these levels in descending
order of priority will ensure that
appropriate alarm signals and messages
are provided first to the zones
immediately at risk.
Compliant, if properly installed.
Responsibility of the installer.
4.3.2 Operational priorities
If the voice alarm system is capable of
operation in fully automatic mode, a
facility shall always be available to
control:
a The type of pre-recorded message
being broadcast.
Compliant, if properly installed:
Input contact configured to
start a call with a pre-
recorded message.
Running message can be
overridden by higher priority
automatic started messages.
Running message can be
overridden by higher priority
manually started messages.
Running message can always
be overridden by the
emergency microphone.
b The distribution of messages to
different zones.
Compliant.
c Real-time instructions or information
to occupants via the emergency
microphone (if any).
Compliant, if properly installed.
Manual selection of loudspeaker
zones is supported.
Plena Appendices | en 121
Bosch Security Systems B.V. Installation and Operation manual 2013.07 | V2.0 |