Clause / Requirement
Compliance Signature
9.3.3 If the indication is on an
alphanumeric display, which cannot
simultaneously indicate all of the
disablements because of its limited
capacity, at least the following shall
apply:
a the presence of disablement
indications which have been
suppressed shall be indicated;
b suppressed disablement indications
shall be capable of being displayed
by means of a manual operation at
access level 1 or 2 which
interrogates only disablement
indications.
9.4 Disablements and their indication
Voice alarm zones may be capable of
being independently disabled and re-
enabled. In this case the disablements
shall be indicated by means of separate
light emitting indicators per zone
and/or an alphanumeric display. The
indications shall not be suppressed
during the voice alarm condition.
9.5 Transmission of the disablement
condition
The VACIE shall have provision for
transmitting, by means of a general
disablement signal, all disablement
conditions specified in this clause.
10 Voice alarm manual control (option with requirements)
Clause / Requirement
Compliance Signature
10.1 General requirements Plena Voice Alarm System is
compliant.
The VACIE may have provision for
manually activating the voice alarm
output condition. If a voice alarm output
control facility is provided the following
shall apply:
Plena Appendices | en 159
Bosch Security Systems B.V. Installation and Operation manual 2013.07 | V2.0 |