Clause / Requirement Compliance Signature
5 information on the communication
parameters employed on each
transmission path,
This is described in the respective
manuals.
6 recommended cable parameters
for each transmission path, and
This is described in the respective
manuals.
7 fuse ratings; Main fuse ratings are described.
c specified means to limit the
consequences of fault (see 13.5.2);
The IUI describes the following
means to limit the consequences
of fault:
Switchover to spare (standby)
amplifiers
Audio/control input
supervision
Backup power supply
Loudspeaker line supervision
The ability of the emergency
microphone to make a ‘fail
safe’ call in case of a
controller defect
A/B group wiring of
loudspeakers
d configuring and commissioning
instructions;
Configuring and commissioning
instructions are included in the
IUI/SCM (installation and user
instruction and software
configuration manual).
e operating instructions; Operating instructions are included
in the IUI.
f maintenance information. Maintenance information of the
Plena Voice Alarm System is
included in the IUI.
13.2.2 The manufacturer shall prepare
design documentation that shall be
submitted to the testing authority
together with the VACIE. This
documentation shall include drawings,
parts lists, block diagrams, circuit
diagrams and a functional description to
such an extent that compliance with this
European Standard may be checked and
that a general assessment of the
mechanical and electrical design is made
possible.
All of the mentioned design
documentation is available as TPD
for inspection by testing
authorities.
Plena Appendices | en 167
Bosch Security Systems B.V. Installation and Operation manual 2013.07 | V2.0 |