Clause / Requirement Compliance Signature
13.8.3 Mandatory indications on an
alphanumeric display shall be legible for
at least one hour following the display of
a new indication of the voice alarm
condition and at least 5 minutes for fault
or disablement conditions, at 0,8 m
distance, in ambient light intensities from
5 to 500 lux, at any angle from the normal
to the plane of the display up to
– 22.5º when viewed from each side,
and
– 15º when viewed from above and
below.
13.9 Indication colors Plena Voice Alarm System is
compliant.
13.9.1 The colors of the general and
specific indications from light emitting
indicators shall be
a red for indications of voice alarms; The system status LED of Plena
Voice Alarm System call stations is
on (red) when the system is in the
voice alarm condition. The
indicators on the controller and
remote control panels are red. The
installer is responsible for
connecting a red light emitting
indicator to a ‘Visual EVAC
indicator’ output contact of the
Plena Voice Alarm System. All zone
indicators in emergency mode are
red.
178 en | Appendices Plena
2013.07 | V2.0 | Installation and Operation manual Bosch Security Systems B.V.