7-10 Basic parameterization REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
29 = I parblock bit3 (weighting 2
3
:
Changes-over the specific motor
data
30 = I parblock bit4 (weighting 2
4
:
Changes-over the specific motor
data
32 = IN no alarm. ext. (IN=input which is
only active in the “STANDARD” mode)
33 = IN no fault ext.
34 = IN fault reset
35 = IN fmin select
36 = IN direct. rotat.
37 = IN no volt. disc.
38 = IN no fast stop
39 = IN RFG parking
40 = IN RFG-up stop
41 = IN motp. faster
42 = IN motp. slower
43 = IN ALM sensitivity up
44 = IN ALM sensitivity down
45 = IN ALM autom. sensitive adjust.
start/stop
46 = IN ALM inhibit, sparking
47 = IN ALM inhibit, load limit
52 = IT no alarm. ext. (IT=input which is
only active in the “TEST” mode)
53 = IT no fault ext.
54 = IT fault reset
55 = IT fmin select
56 = IT direct. rotat.
57 = IT no volt. disc.
58 = IT no fast stop
59 = IT RFG park
60 = IT RFG-up stop
61 = IT motp. faster
62 = IT motp. slower
63 = IT ALM sensitivity up
64 = IT ALM sensitivity down
65 = IT ALM autom. sensitive adjust.
start/stop
66 = IT ALM inhibit, sparking
67 = IT ALM inhibit, load limit
70 = O no function
71 = O ready to switch-on (O=output)
72 = O status: Ready to switch-on
73 = O ready
74 = O status: Ready
75 = O operation (run)
76 = O no fault
77 = O power-on inhibit
78 = O no alarm
79 = O motor rotating 1 (on & ((t <x.x sec) or
(i>x.xx %)))
80 = O motor rotating 2 (on & (fact > fmin) &
(i> x.xx %))
81 = O direction of rotation, clockwise
82 = O current limiting
83 = O not mot. alarm temp. (alarm:
Motor temperature)
84 = O not motovertemp (fault:
Motor temperature)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01