7-18 Basic parameterization REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
U
a
U
b
U
c/d
f
a
f
b
f
c
f
d
a
b
cd
f [Hz]
U [V]
V
boost
Fig. 7-5: V/Hz characteristic diagram
).0117().0120( XPIXXPRV
sdratedSboost
×=
Active load monitor WLM
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0896 ALM sparking sensi-
tivity 1 = Fixed values
2 = Analog input 0..±10V
3 = Analog input 0..+20mA
4 = Analog input 4..+20mA
5 = Opt. an.inp 0..±10V (opt. =
optional)
6 = Opt. an.inp 0..+20mA
7 = Opt. an.inp. 4..+20mA
8 = PC (PC with REFUwin via the
service interface)
9 = Bus SS1
10 = Bus SS2
11 = Bus SS4
12 = Analog input 2..+10V
13 = Bus SS6
Fixed values
1 ... 13
1
0897 ALM load limit
1 = Fixed values
2 = Analog input 0..±10V
3 = Analog input 0..+20mA
4 = Analog input 4..+20mA
5 = Opt. an.inp 0..±10V (opt. =
optional)
6 = Opt. an.inp 0..+20mA
7 = Opt. an.inp 4..+20mA
8 = PC (PC with REFUwin via the
service interface)
9 = Bus SS1
10 = Bus SS2
11 = Bus SS4
12 = Analog input 2..+10V
13 = Bus SS6
Fixed values
1 ... 13
1
1203.XX Fixed value sensitiv-
ity
Supplementary parameter for “fixed values” from
P0896
The appropriate sparking sensitivity is manually set
0.30 %
0.00 ... 100.00 %
1
1216.XX
1)
Fixed value load limit Supplementary parameter for “fixed values” from
P0897
Sets the corresponding load limit
80.00 %
0.00 ... 190.00 %
1