REFUspeed RS51 Basic parameterization 7-19
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0297.00 Analog input window Supplementary parameter for analog input.
The analog setpoint smoothing is specified in a win-
dow as a%.
For example: Window width = 1 %. A change of the
actual setpoint is only accepted if a change greater
than 0.99 % of the possible final value is detected at
the analog input.
0.50 %
0.00 ... 20.00 %
1
0200.00 Analog input norm. Supplementary parameter for analog input.
The analog input normalization refers to the frequency
normalization P0390.
100 %
-199.99 ... 199.99
%
2
0202.00 Analog input offs. Supplementary parameter for analog input.
Analog input offset
0.00 %
-199.99 ... 199.99
%
2
0203.00 Analog input sign. Supplementary parameter for analog input.
Analog input signal
0= direct
1 = absolute value
2= inverted
3 = absolute value, inverted
Direct
0 ... 3
2
0204.00 Analog input filter. Supplementary parameter for analog input.
Analog input filter time to smooth the analog signal.
2ms
0 ... 10000 ms
2
0564.nn Reaction on I < 4mA Supplementary parameter for analog input 4...+20
mA.
Response for I<4mA
0 = no action
1= warning
2 = fault
nn = 00 for NORMAL
nn = 01 for TEST
Warning
0 ... 2
2
1218 Hysteresis,
load limit Hysteresis of the load limit comparator. This hysteresis
is effective in both directions of the selected load limit.
5.00 %
0.00 % ... 100.00
%
1
Additional functions
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0282.YY Rounding ramp up
Rounding-off times UP for the ramp-function genera-
tor.
This is used for jerk limiting when starting; this is gen-
erally not more than 1/10 of the ramp time.
0.000 s
0.000 ... 800.00 s
1
0283.YY
2)
Rounding ramp down
Diagram, ramp-up/ramp-down ramp with rounding-off
0.000 s
0.000 ... 800.00 s
1