ALARM COUNT
This macro nags you every hour until you respond to the fact that there a 10 or more alarms. This could be set to
run at startup so it is always on. During maintenance you could stop it manually.
1
If alarm count on site "BURK-FM" < 10, goto line 1
2
Send email message “more than 10 alarms!” to email
list "Chief"
3
Wait for 01:00:00
4
Goto line 1
TRANSMITTER START SEQUENCE
Here is a tube transmitter startup that skips the filament turn on and delay if filaments are already on.
1
If status of "TX-A FIL ON / TX-A TX-A FIL OFF" on
site "BURK-FM" = "TX-A FIL ON", goto line 4
2
Raise "TX-A FIL ON" on site "BURK-FM" for
[default]
3
Wait for 00:05:00
4
Raise "TX-A RF ON" on site "BURK-FM" for
[default]
5
End macro