EasyManua.ls Logo

Camus Hydronics Avenger Series - Page 44

Camus Hydronics Avenger Series
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
Hydronic Heating
Modulation: Boiler Inlet, Boiler Fixed Setpoint Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
Boiler operates at a
fixed CH setpoint
Modulates on boiler
inlet sensor (default)
Heat demand is
generated when inlet
temperature drops
below setpoint minus
on hysteresis
If set to local enable
constant pumping is
required
For remote enable
intermittent pumping is
allowed.
1) Place toggle switch to LOCAL
2) Press and
3) Press [CH Central Heat Configuration]
4) Press the to arrive at Setpoint
5) Select Setpoint source: Local
6) Enter desired Setpoint
7) Place toggle switch to REMOTE for remote enable operation (if required)
Modulation: Boiler Inlet, Outdoor Reset Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
Boiler operates with
variable setpoint
determined by outdoor
reset curve
Modulates on inlet
sensor (default)
Heat demand is
generated when inlet
temperature drops
below setpoint minus
on hysteresis
1) Connect outdoor sensor to System/Outdoor contacts
2) Place toggle switch to LOCAL
3) Press and
4) Press Outdoor Reset Configuration
5) Select Enable: Enable
6) Select Maximum outdoor temperature (WWSD)
7) Select Minimum outdoor temperature (Outdoor Design)
8) Select Low Water Temperature (Min. Water Temp.)
9) Select Outdoor boost maximum off point (Design Max.)
10) Press [CH Central Heat Configuration]
11) Select Outdoor Reset = Enabled
12) Set CH Setpoint = Outdoor boost maximum off point
13) Press Sensor Configuration
14) Select Outdoor temperature source = S5 (J8-11) sensor
15) Place toggle switch to REMOTE for remote operation (if required)

Table of Contents

Related product manuals