S
stoutjustinSep 18, 2025
What does 14 flashes mean on CaptiveAire TANK Fire Extinguisher?
- SschneiderjefferySep 18, 2025
If the system flashes fourteen times, check the dip switches on all boards and RS-485 network wires connecting boards.
What does 14 flashes mean on CaptiveAire TANK Fire Extinguisher?
If the system flashes fourteen times, check the dip switches on all boards and RS-485 network wires connecting boards.
Why is the audible alarm on my CaptiveAire TANK activated?
The audible alarm is activated because the fire system has been activated. To resolve this, first verify that the fire is completely out, and then reset the fire system.
How to turn off CaptiveAire Fire Extinguisher system that won't turn off?
If the fire system will not turn off, it could be due to two reasons: 1. The duct sensor is hot, meaning heat has activated it. Remove the heat source or allow the system to extinguish the fire. Once the heat source is gone, press the reset button on the electrical control package. 2. The Remote Manual Actuation Device has been pushed. Reset the remote push station (twist clockwise until reset) after the fire is out, and then press the reset button on the electrical control package.
What to do if the exhaust fan is on but the supply fan won't start in my CaptiveAire TANK?
If the exhaust fan is running but the supply fan won't start, it could be due to: * A broken supply fan belt. If this is the case, replace the fan belt. * The fire system not being armed. The fire system distributor must arm the fire system.
What does 15 flashes mean on CaptiveAire Fire Extinguisher?
If the system flashes fifteen times, check all hoods in the CORE network for faults.
What does 16 flashes mean on CaptiveAire TANK Fire Extinguisher?
If the system flashes sixteen times, check all PCUs in the CORE network for faults.
What does 4 flashes mean on CaptiveAire Fire Extinguisher?
If the system flashes four times, check supervised Pressure Regulating Valves (optional) and Pressure Switches (optional).
What does 7 flashes mean on CaptiveAire TANK Fire Extinguisher?
If the system flashes seven times, check the wiring to all the manual actuation devices (push/pull stations) and fire sensors for shorts to ground, replace as needed. Refer to “Supervised Loop Electrical Details” on page 46.
What causes Supervised Loop Fault in CaptiveAire TANK Fire Extinguisher?
A Supervised Loop Fault can occur due to several reasons: * Open Supervised Loop between Terminals 21 and 24: Locate and repair faulty wiring in the 21-24 supervised loop. * Open Supervised Loop between Terminals 22 and 23: Locate and repair faulty wiring in the 22-23 supervised loop. * Open Supervised Loop Push- Station (Terminals 101 and 104): Locate and repair faulty wiring in the 101-104 supervised loop. * Open Supervised Loop Push- Station (Terminals 102 and 103): Locate and repair faulty wiring in the 102-103 supervised loop.
What to do if gas valve does not close in CaptiveAire Fire Extinguisher?
If the gas valve doesn't close, it's likely due to debris on the gas valve seal. Fully clean the gas valve and strainer to resolve this.
Provides a general description of the fire suppression system's function and components.
Explains the typical installation and mounting of agent storage cylinders within the cabinet.
Step-by-step guide for replacing a faulty primary actuator kit.
Instructions for replacing a malfunctioning secondary valve actuator.
Details flushing the network using a spare or test cylinder.
Instructions for safely removing cylinders from the system for maintenance or storage.
| Agent Type | Wet Chemical |
|---|---|
| Application | Restaurant, Commercial Kitchen |
| Extinguishing Agent | Wet Chemical |
| Operating Pressure | 100 psi |
| Discharge Time | 40 seconds |
| Weight | 22 lbs |
| Material | Steel Cylinder |
| Standards | ANSI/UL 8, ULC S554, NFPA 10 |
Loading...