TROUBLESHOOTING
Table 16 lists out causes and corrective actions for possible problems with the system. Review this list prior to
consulting the manufacturer.
Table 16 - Fire Protection System Troubleshooting
Problem Potential Cause Corrective Action
Exhaust Fan is On and Supply Fan
will not Start
Broken supply fan belt Replace fan belt.
Fire system not armed
Fire system distributor must arm fire
system.
Fire System Activated Light On Fire system is activated
Verify fire is out and reset fire
system.
Audible Alarm is On Fire system is activated
Verify fire is out and reset fire
system.
A fault code is flashing on the “Fire
System Activated” light
A fault has been detected in the Fire
Protection System
Count the flashes and refer to
“Appliance Shutdown in Fault
Conditions” on page 55.
Gas Valve does not Close Debris on gas valve seal Fully clean gas valve and strainer.
Fire System will not Turn Off
Duct sensor is hot
Heat has activated the duct sensor.
Remove heat source or let the
system extinguish the fire. Once heat
source or problem is resolved, press
reset button on the face of the
electrical control package.
Remote Manual Actuation Device
has been pushed
Reset remote push station once fire
is out and press reset button on the
face of the electrical control package.
Reset remote push station by
twisting clockwise until reset.