8. CONFIGURATION
Entering MODEL MANAGEMENT MODEL
CONFIGURATION ALARMS and choosing
the devices on the two lines from the list one at
a time, the alarms can be enabled or disabled
and the priority set (the priority of an alarm will
be indicated in the list with a diff erent colour,
depending on the level).
Then return to the previous menu and enter
LOG/GRAPH/HACCP/MAIN VIEW DEVICE
DETAIL VARIABLE DETAIL ; a screen will
be displayed for selecting: the frequency for
recording the value of the variable, the colour
used to draw the curve showing the trend
of this variable on the graph, and if required
include the variable in the report and/or on
the graph.
In the list of variables logged, the
columns have the following meanings:
Freq: sampling frequency.
G: variable displayed on the graph.
P: variable included in the HACCP report.
M: variable included in the main list of
devices in the installation (INSTALLATION
menu).
The data recording period depends on the
sample time, as shown in the table below:
Sampling time Recording period
30 s 13 days
1 min 26 days
3 min 80 days
5 min 133 days
15 min 400 days