Low value of PID feedback
loss
Detection time for low value
of PID feedback loss
High value of PID feedback
loss
Detection time for high value
of PID feedback loss
When the PID feedback value is not in the range of F0.24 and F0.28, and lasting time attains the
set of F0.25/F0.28, then inverter will report Err19(PID feedback loss).
Unit’s place: operation selection when power off
0: No PID operation at stop
1: PID operation at stop
It is used to select whether to continue PID operation in the state of stop. Generally, the PID
operation stops when the AC drives stops.
Ten’s place: PID output is limited by output frequency
0: No limit
1: limit
When using PID regulation, Setting “1”can prevent output lags caused by the existence of
acceleration and deceleration.
Hundred’s place: Action selection when using UP/DOWN function to modify the frequency
in PID mode.
0:Zero clearing when power off.
Clear the value(increased or decreased) caused by UP/DOWN function when power off
1:Keep the value when power off.
Keep the value (increased or decreased) caused by UP/DOWN function when power off
Thousand’s place: Select whether to detect PID feedback loss or not at stop.
0: No detection at stop.
1: Do detection at stop
Ten thousand’s place: Select action for PID feedback loss
0: Report fault
1: Ramp to stop
2: Continue running
UP/DOWN speed of PID
digital given
Range:0.0~100%(0.0%
invalid)
This function code is to set the speed of UP/DOWN function, value 100% corresponding to 50Hz.
This function code set the upper limit source of PID mode;
0:F0.22
1:F0.22*VP(Potentiometer on keypad)
2:F0.22*AI1
3:F0.22*AI2
4:F0.22*HI(Pulse input ,DI7)
5:F0.22*AI3 (VSX Only)
This function code set the lower limit source of PID mode;
0:F0.23
1:F0.23*VP(Potentiometer on keypad)
2:F0.23*AI1
3:F0.23*AI2
4:F0.23*HI(Pulse input ,DI7)
5:F0.23*AI3 (VSX Only)