Emotron VS Series Quick Start Guide
- 83 -
Chapter 6 Specification of Parameters
Group A0 System Parameters
Setting of password:
A number greater than 100 could be set as a user password by entering this password into A0.00
and pressing ENT key to confirm once, the password setting will take effect as long as there is
no operation on keypad within 5 minutes, or cutting the power off and power up again . After a
password has been set and taken effect, you must enter the correct password in order to enter the
menu. If the entered password is incorrect you cannot view or modify parameters.
Change password:
Access A0.00 after entering the original password (at this point, A0.00 displays setting of user
password) and set the new password following the above-noted procedure.
Password clearance:
Access A0.00 after entering the original password (at this point, A0.00 displays setting of user
password); A0.00 is set to 0 and press ENT key to make confirmation. In this way, password is
successfully cleared and the password protection function is disabled.
0: Display all parameters
1: Only display A0.00, A0.01 and user-defined parameters
2: Only display A0.00, A0.01 and the parameters different with factory default
0: All parameter programming allowed
1: Only this parameter programming allowed
G/P type display
(VSX Only)
0: G type (constant torque load)
1: P type (variable torque load e.g. fan and pump)
0: No operation
1: Restore all parameters to factory default (excluding motor parameters)
If A0.04 is set to 1, most function codes are restored to the default settings except motor
parameters, fault records, accumulative running time, and accumulative power-on time.
2: Clear fault record
If A0.04 is set to 2, all fault record of Group U1 will be cleared.
3: Back up current user parameters
If A0.04 is set to 3, the current parameter settings are backed up, helping you to restore the
setting if incorrect parameter setting is performed.
4: Restore all parameters to backup parameters
If A0.04 is set to 4, the previous backup user parameters are restored.
5: Restore factory default (include motor parameters)
The same as function 1, but this include motor parameters
6: Power consumption zero clearing
After setting A0.04 as 6, U0.35 parameter cleared to zero
0: No operation
1: Upload all parameters other than Group U to UP/DOWNLOAD
2: Download all parameters of UP/DOWNLOAD other than d0~d1 to drive
3: Download all parameters of UP/DOWNLOAD to drive
*: UP/DOWNLOAD is optional parts
0: Editable via keypad and RS485
1: Editable via keypad
2: Editable via RS485