Emotron VS Series Quick Start Guide
- 13 -
Recommended MPPT
Voltage Range
Grid or backup generator input
Three phase 415V(-20%~20%)
0~600.00Hz(Default 0~50.00Hz)
Lightening protection, over-current, overvoltage, output phase-lose,
under-load, under-voltage, short circuit, overheating, water pump dry
run etc.
No direct sunshine, no dust, corrosive gas, combustible gas, oil mist,
steam, dripping or salinity etc.
0~2000 m
.Above 1000m, derate the rated current capacity by 1% for every
100m
-10℃~50℃ (Above 40℃~ with deration)
Above 40℃, derate the rated current capacity by 1% for every 1℃.