3.0 GETTING STARTED
3-2 Cheetah Xi Programming Manual
Rev 1, 09/2013 P/N: 06-651
3.2 PASSWORD PROTECTION
Access to the Cheetah Xi system’s control and function switches are restricted by the enclosure door. With
the door closed and locked, responding personnel can only view system events on the panel display and use
the accessible EVENT STEP keys to filter through the systems event history. Opening the enclosure door
provides access to the systems Control and Function keys, which allows greater system operation
capabilities. With the enclosure door open, responding personnel have the ability to Silence or Acknowledge
system events, initiate Drill commands and Reset the system. In addition, the system operator has limited
access to the systems menus and features without needing to enter a system password.
Access to the Cheetah Xi’s menu system is password protected to restrict access to those who require it.
Each Cheetah Xi allows up to eight (8) User level passwords and a single System Administrator password to
be assigned by the system installer. The available security access levels are described as follows:
Password
Level
Designation Privileges
Default
(door panel closed)
View system events on LCD display
Access to STEP keys for reviewing system history
1 Customer
(door panel open – no
password entered)
All default privileges, plus:
Access to system control switches for executing system Drill,
Acknowledge, Silence and Reset
History menu (view only)
Diagnostic menus (view only)
Maintenance menu: Read Device and Device Address (all
other menu features are view only)
IR Communication (enable/disable)
2 USER
(Level 2 password entered –
eight available)
All default and Level 1 privileges, plus:
Configuration menus: Configuration check and set system time
(all other menu features are view only).
Maintenance menu: Device Replace, Walktest, and Buzzer Off
Level 2 passwords are assigned during system configuration
3 SYSTEM ADMINISTRATOR
(Level 3 password entered)
All default, Level 1 and Level 2 privileges, plus:
Full access to all system menus
Default password is set by the factory prior to shipment. Can
be changed in the field.
Exhibit 3-2: Password Access Levels