Commissioning
4-16
750-382
CBT
Changing parameter settings
To access the CB Falcon configuration menu, press <Configure> on the Status page.
From the Configuration menu (Figure 4-6), select the parameter group to be changed.
Some parameters require a password entry before allowing changes. The <Login> button will appear when any
password-protected parameter is displayed on the screen.
Press <Login> to display the alphanumeric keyboard. Enter password and press <OK>
Change parameter settings by selecting the parameter on the page. A dialog box appears with controls allowing
the user to change the selected value. Press <Clear> to clear the current value. Enter the new value and press
<OK> (press <Cancel> to leave the parameter unchanged).
Lead Lag Slave
Configuration
Slave mode Service Equalize runtime 564
Lead Lag Slave
Configuration
Base load rate Service 3000rpm RPM 566
Lead Lag Slave
Configuration
Fan during off cycle
rate
Service 0rpm 0rpm 4000rpm RPM 567
Lead Lag Slave
Configuration
Slave sequence order Service 0 1 to 8 568
Lead Lag Slave
Configuration
Lead lag slave
demand to firing
delay
Service 3m 0s mmm ss 570
Lead Lag Slave
Configuration
Modbus address Service 1 1 to 8 568
TABLE 4- 1.
CB Falcon factory parameter settings - Model CBT-M (Continued)
Parameter Group Parameter Name Access Min.
Range
Default Setting Max.
Range
Parameter Units Installation
Setting
Modbus
Register
(dec)
FIGURE 4-10. Configuration menu