CB FALCON
750-265 4
FEATURES
Safety and Boiler Protection
Hydronic Control
Frost Protection, Slow Start, Anti-condensate, Boiler Delta-
T, Stack Limit, Boiler Limit, DHW Limit, Outlet T-Rise Limit
Steam Control
Slow Start, Stack Limit
Integrated Control Functions
Primary Flame Safeguard Control
Internal or external spark generator
Algorithm Prioritization
Firing Rate Limiting
Hydronic Control
Anti-Condensate, Stack Limit, Boiler Delta-T,
Boiler Slow Start, Outlet Limit
Steam Control
Stack Limit
PID Load Control
Hydronic Control
CH (Central Heat)
DHW (Domestic Hot Water)
Steam Control
•Steam
Remote Reset
TOD (Time of Day)
PWM for Variable Frequency Drives
Auxiliary Output Control
Hydronic Control for Pumps
3 outputs, 5 different programmable
features)
Steam Control
3 programmable output features
Burner Demand sources
Hydronic Control
CH, DHW and Frost Protection
Steam Control
Steam sensor
Loops of Control
Hydronic Control has two loops of Control
•CH
DHW
Steam Control has One loop of Control
•Steam
High Limit and Control (Meets UL 353)
Hydronic Control
CH, DHW and Stack
Steam Control
•Stack
Fifteen Item Fault Code History including equipment status
at time of lockout
Fifteen Item Alert Code Status including equipment status at
time of internal alerts
24Vac Device Power
Hydronic: 24 or 120Vac Digital I/O models available.
Steam: 120Vac Digital I/O
Flame Signal test jacks (Vdc)
Three Status LEDs
Power
•Flame
•Alarm
Flame Sensing
Ultraviolet (C7027, C7035, C7044 Sensors)
Flame Rod
Single Element (Internal spark generator
and flame sense using the same element)
Dual Element (separate elements for ignition
spark and flame sense)
Inputs
Analog Inputs
NTC Sensor Inputs (10kohm or 12kohm)
NOTE:12kohm and 10kohm single sensors cannot be
used for Limit Application functions (10kohm
dual sensors only).
Hydronic Control
Outlet Limit And Temperature
DHW Limit and Temperature
Stack Limit and Temperature
Inlet Temperature
Outdoor Temperature
Steam Control
Stack Limit and Temperature
Other Analog Inputs
PWM Feedback
Flame Signal from either a Flame Rod or
Ultraviolet Detector
4-20mA Control Input, Remote Setpoint,
Remote Firing Rate
4-20mA Steam Input Pressure (15 or 150
psi)
Digital Inputs
Pre Ignition Interlock (Programmable)
LCI (Load [or Limit] Control Input) (Programmable)
Interlock (Programmable)
Annunciation (8 Programmable) (6 Programmable
plus High Fire and Low Fire Switch Interlocks—
model specific)
Remote Reset
TOD (Time of Day)
Outputs
Analog Outputs
Modulation
•4-20mA
•0-10 Vdc
PWM for Variable Frequency Drives
Digital Outputs
Auxiliary Output Control
Hydronic Control for Pumps
3 outputs, 5 different programmable
features)
Steam Control
3 programmable output features
Combustion Blower
External Ignition
Pilot Valve
•Main Valve
•Alarm