EasyManuals Logo

CleaverBrooks CFC-1000 User Manual

CleaverBrooks CFC-1000
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #229 background imageLoading...
Page #229 background image
CB FALCON
105 750-265
APPENDIX C: LOCKOUT AND HOLD
CODES
To support the recommended Troubleshooting, the Falcon has
an Alert File. Review the Alert history for possible trends that
may have been occurring prior to the actual Lockout.
Note Column: H= Hold message; L=Lockout message; H or L=
either Hold or Lockout depending on Parameter Configuration
Table 49. Falcon Lockout and Hold Codes.
Code Description Recommended Troubleshooting of Lockout Codes NOTE
Safety Data Faults
1 Unconfigured safety data 1. New Device, complete device configuration and safety
verification.
2. If fault repeats, replace module.
L
2 Waiting for safety data verification 1. Device in Configuration mode and safety parameters
need verification and a device needs reset to complete
verification.
2. Configuration ended without verification, re enter
configuration, verify safety parameters and reset device to
complete verification.
3. If fault repeats, replace module.
L
Internal Operation Errors

Table of Contents