CB FALCON
750-265 104
Stack limit delay Read Only 5m 0s mmm:ss
Delta-T enable Read Only Disabled
Delta-T degrees Read Only 30°F 17°C
Delta-T response Read Only [ A #b C #d ] A:Lockout
Delta-T delay Read Only 5m 0s mmm:ss
DHW high limit enable Read Only Enabled
DHW high limit setpoint Read Only 32°F 0°C 150°F 66°C 240°F 116°C
DHW high limit response Read Only [ A B #c D ] D:Suspend DHW
CH slow start enable Read Only Disabled
DHW slow start enable Read Only Disabled
Slow start ramp Read Only 10% % | RPM per
minute
Slow start setpoint Read Only 0°F -18°C 20°F -7°C 180°F 82°C
CH anticondensation enable Read Only Disabled
CH anticondensation
setpoint
Read Only 32°F 0°C 135°F 57°C 240°F 116°C
CH anticondensation pump
Force Off
Read Only Disabled
DHW anticondensation
enable
Read Only Disabled
DHW anticondensation
setpoint
Read Only 32°F 0°C 135°F 57°C 240°F 116°C
DHW anticondensation pump
force off
Read Only Disabled
Anticondensation > Outlet
limit
Read Only No/False/Off
Anticondensation > Delta-T Read Only No/False/Off
Anticondensation > Stack
limit
Read Only No/False/Off
Anticondensation > Slow
start
Read Only Yes/True/On
Anticondensation > Forced
rate
Read Only Yes/True/On
CH ODR max outdoor
temperature
Read Only 80°F 27°C
CH ODR min outdoor
temperature
Read Only 0°F -18°C
CH ODR min water
temperature
Read Only 32°F 0°C 50°F 10°C 240°F 116°C
CH frost protection enable Read Only Disabled
DHW frost protection enable Read Only Disabled
Outdoor frost protection
setpoint
Read Only 32°F 0°C
Table 48. Example of a Completed Device Parameter Worksheet. (Continued)
Parameter Name
Customer
Choice - Hidden,
Read Only or
Password
protected Minimum Range Default Setting Maximum Range Parameter Units