OnLeave A slave in the OnLeave state remains that way until
the ProcessSlaveStatus moves it to some other state.
Disabled A slave in the Disabled state remains that way until
the ProcessSlaveStatus moves it to Recovering.
Demand and Priority
Fig. 30. LL Master demand sources.
CH DEMAND
WARM WEATHER SHUTDOWN (WW-SD)
LL MASTER DEMAND SOURCES
CENTRAL HEAT
LL CH DEMAND SWITCH
FROST PROTECTION
WARM WEATHER SHUTDOWN
LL WARM WEATHER SHUTDOWN ENABLE
LL WARM WEATHER SHUTDOWN SETPOINT
LL MASTER FROST PROTECT ENABLE
DISABLE LL CH
STAT
EnviraCOM REMOTE STAT
MASTER
HEAT DEMANDS
THE SOURCES ASKING
FOR HEAT. USED FOR
PUMP CONTROL.
MASTER
ACTIVE SERVICE
THE DEMAND SOURCE
THAT IS CURRENTLY
CONTROLLING THE LL
MASTER.
Table 37. CH Demand Parameters.
Parameter Comment
LL CH demand switch Disable, STAT, EnviraCOM Remote Stat
The inputs that can function as the CH demand switch are: STAT, EnvironCOM Remote Stat.
If the CH demand switch value is Disable, the LL master does not respond to CH demand.
Table 38. Warm Weather Shutdown (WW-SD) Parameters.
Parameter Comment
Warm weather shutdown enable Disable, Shutdown after demands have ended, Shutdown immediately