CB FALCON MODBUS COMMUNICATION
15
Table 4. CB Falcon Modbus register map
00E5 0229 Purge rate proving R/W U16
SAFETY parameter
f
:
0=None,
1=High Fire Switch (HFS),
2=Fan speed
00E6 0230 Lightoff rate proving R/W U16
SAFETY parameter
f
:
0=None,
1=(Low Fire Switch) LFS,
2=Fan speed,
3=Fan speed, except during ignition
00E7 0231 Prepurge time R/W U16
SAFETY parameter
f
:
0-64800 seconds (18 hours), 0xFFFF=Not configured
00E8 0232 Pre-ignition time R/W U16
SAFETY parameter
f
:
0-64800 seconds (18 hours), 0xFFFF=Not configured
00E9 0233
Pilot flame establishing
period (PFEP)
R/W U16
SAFETY parameter
f
:
0=None,
1=4 seconds,
2=10 seconds,
3=15 seconds,
0xFFFF=Not configured
00EA 0234
Main flame establishing
period (MFEP)
R/W U16
SAFETY parameter
f
:
0=None,
1=5 seconds,
2=10 seconds,
3=15 seconds,
0xFFFF=Not configured
00EB 0235 Run stabilization time R/W U16
SAFETY parameter
f
:
0-64800 seconds (18 hours), 0xFFFF=Not configured
00EC 0236 Postpurge time R/W U16
SAFETY parameter
f
:
0-64800 seconds (18 hours), 0xFFFF=Not configured
00ED 0237 Interlock start check enable R/W U16
SAFETY parameter
f
:
0=No ILK check,
1=ILK check
00EE 0238 Interlock open response R/W U16
SAFETY parameter
f
0=Lockout, 1=Recycle
00EF 0239 Ignite failure response R/W U16
SAFETY parameter
e
:
0=Lockout,
1=Continuous recycle,
2=Retry, recycle & hold,
3=Retry, recycle & lockout
00F0 0240 Ignite failure retries R/W U16
SAFETY parameter
f
:
0=None,
1=3 times,
2=5 times,
3=1 time,
0xFFFF=Not configured
00F1 0241 Ignite failure delay R/W U16
SAFETY parameter
f
:
0-64800 seconds (18 hours), 0xFFFF=Not configured
00F2 0242
MFEP flame failure
response
R/W U16
SAFETY parameter
f
:
0=Lockout, 1=Recycle
00F3 0243 Run flame failure response R/W U16
SAFETY parameter
f
:
0=Lockout, 1=Recycle
00F4 0244 Pilot test hold R/W U16 0=Disable, 1=Enable
00F5 0245 RESERVED R/W U16