EasyManua.ls Logo

Climate Technologies Touch Pad Control - System Configuration and Commissioning

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi-Appliance Touch Pad
PNE2004 Series Control
Page 43
Controls – Installation / Setu
p
/ Commissionin
g
Evaporative Air Conditioning Setup
SETTING THE WATER MANAGEMENT SYSTEMS PARAMETERS AND VALUES
There are 3 setup modes available in the water management as set out in the table below. The use of
these modes is based on 2 selection criteria:
PRECOOL Parameter 2: The option to have the pump run for 2 minutes before the fan starts. The
benefit is that when the fan starts cool air will be delivered immediately.
PREFILL – Parameter 4: The option to have the pump prefill the tank for 2 minutes before starting the
pump operation.
DUMP VALVES Parameter 1 & 3: These setup options will only be used when the evaporative air
conditioner has a dump valve fitted .
Parameter 1 – Gives a 1 hour delay before dumping the water from the
tank. This function is particularly useful when the unit is being used in
THERM mode as it will stop premature dumping of the water.
Parameter 3 – This provides the hour dumping cycles available. These
should be set according to water hardness in the supply.
Water Management Table – Evaporative Air Conditioning.
Installer
Maintenance
Parameter Default OFF
Value
ON Value
Dump Delay after
shutdown
1 01 00 = OFF 01= 1 hr
Pre-Cool 2 00 00 = OFF 01 = 3.0 min
Dump Interval 3 12 00 = OFF 01, 02, 04, 08, 12,
24 hrs
Pre-Fill 4 00 00= OFF 01

Table of Contents