ID-FLX Lite & Telecom Global Guide
114
Setpoint group Engine parameters Related FW 2.5.0
Range [units] OFF/CU: AI1 .. CU: AI9/AIO: AI1 .. AIO: AI4 [-]
Default value OFF -
Step -
Comm object 15989 Related applications N/A
Description
This setpoint is used for selection of analog input, which is used for temperature measurement used for
variable preheating time calculation. See description of PREHEAT (PAGE 198).
PreheatSensor
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 1 .. 60 [s]
Default value 5 -
Step 1
Comm object 8256 Related applications
Description
This setpoint is giving maximum time limit of engine cranking.
MaxCrank time
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 5 .. 60 [s]
Default value 8 -
Step 1
Comm object 8257 Related applications
Description
Pause between crank (engine start) attempts.
CrnkFail pause
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 1 .. 10 [-]
Default value 3 -
Step 1
Comm object 8255 Related applications
Description
Maximum number of crank (engine start) attempts.
Crank attempts
6 back to List of setpoints