ID-FLX Lite & Telecom Global Guide
130
Setpoint group Load limit Related FW 2.5.0
Range [units]
CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8, CU:AI9,
AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4, RPM-BI3 [-]
Default value CU:AI1 YES
Step -
Comm object 11839 Related applications
Description
This is comparator with hysteresis analog input selection from controller analog inputs or from extension
module inputs. It is also possible to use Binary input 3 in function of RPM detection.
Reg CMP Input
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units] -10000 .. +10000 [-]
Default value 0 YES
Step 1
Comm object 11841 Related applications
Description
Limit to close SPEEDSWITCH (PAGE 217).
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Reg CMP On
6 back to List of setpoints